16 Installer’s Guide
5.5 PGM TIMER
Section 007
If the keypad's on-board PGM is in PGM Timed Mode, the value
programmed in section [007] represents how long the PGM will
remain in its opposite state (see section 5.1 of this manual) after being
activated. To program the timer, enter a 3-digit decimal value (000 to
255) in section [007]. The 3-digit value will be multiplied by the PGM
Base Time of 1 second or 1 minute (see section 5.6 of this manual).
5.6 PGM BASE TIME
Section 005: Option [3]
If the keypad's on-board PGM is set in PGM Timed Mode (see
section 5.4 of this manual) you must define whether the value
programmed in section [007] is in minutes or seconds.
Option [3] OFF = PGM Base Time is 1 second (default)
Option [3] ON = PGM Base Time is 1 minute
5.7 PGM OVERRIDE
Section 005: Option [4]
When PGM Override is enabled, the keypad's on-board PGM will
ignore PGM Activation Events, PGM Deactivation Events, and PGM
Timers. It will remain in its normal state (see section 5.1 of this
manual) until the PGM Override is disabled. This option may be used
to test the PGM connections.
Option [4] OFF = PGM Override disabled (default)
Option [4] ON = PGM Override enabled